This calculator uses the standard BS 7671 20°C copper conductor resistance values (IET On-Site Guide, Table I1) to cross-check and fill in expected ring final or radial circuit results — Zs, Ze, R1, R2, R1+R2, end-to-end conductor readings, and cable length — from whichever readings you already have. For training and estimation only; always verify against on-site measurements.

Circuit & Conductor Setup

Ring final: end-to-end readings taken around the whole ring, crossed over at the board.

Auto-set from standard T&E pairing

Enter What You Know

Fill in any readings you have — leave the rest blank. You don’t need a full set.

Earth fault loop impedance

Continuity (R1 / R2) readings

End-to-end conductor readings

Cable length

Estimates only, based on 20°C copper resistance values with no correction for conductor operating temperature, cable grouping, or ambient temperature. Always confirm against on-site test results and follow IET Guidance Note 3 when completing a formal EICR or Electrical Installation Certificate.

Frequently asked questions

What is R1+R2 on a ring final or radial circuit?

R1+R2 is the combined resistance of the line conductor (R1) and circuit protective conductor (R2) at the point furthest from the consumer unit. On a ring final circuit it equals one quarter of the total end-to-end (r1+r2) loop resistance measured with the ring crossed over at the board. On a radial circuit R1 and R2 are simply the one-way end-to-end resistances of the line and CPC.

Can I enter just one or two readings instead of a full set?

Yes. Enter whatever you already know — for example just Zs and Ze, or just a cable length, or just a Line-Line reading — and the calculator derives every other expected value it can from BS 7671 20°C copper resistance values and the conductor sizes you select. It also flags any readings that don’t agree with each other.

What is the difference between a ring final and a radial circuit here?

On a ring final circuit, the end-to-end conductor resistance (Line-Line, Neutral-Neutral, Earth-Earth) is four times the R1, R2 figure measured at the furthest socket, because current can flow two ways around the ring. On a radial circuit there is only one path, so R1 and R2 equal the full end-to-end resistance. Select the correct circuit type so the calculator applies the right relationship.

Why does Twin and Earth cable auto-select the CPC size?

UK Twin & Earth (T&E) cable is manufactured with standard factory-paired conductor sizes — for example 2.5mm² line with a 1.5mm² CPC. Selecting “Singles / separate CPC” allows any CPC size to be entered independently, as used with separate single-core conductors.