Lighting is taken at 80%. The largest socket circuit is taken in full and the others at half. A cooker is 10 A plus 60% of the rest. Showers, heaters, EV chargers and anything marked fixed are taken at 100%.

Loads

This is a cautious screen, not a copy of the BS 7671 or On-Site Guide tables. The numbers are rounded so a pass sits inside a margin. If the result is close, or if it fails, check the current tables before you decide. Do not put this figure on a certificate in place of the published value. Real diversity allowances are often more generous, which would give a lower demand. Use this as a high-side check. Confirm the assessment method you are required to use before you order a supply or a cut-out.