Same resistance method as the voltage-drop tool, rearranged. Enter a size to get a maximum length, a length to get a minimum size, or both. Single-phase uses 2 × I × R. Three-phase uses √3 × I × R.

Run

Resistance only. Larger cables also have reactance, so BS 7671 Appendix 4 (mV/A/m) is the figure to design with. The 3% and 5% limits are from the origin to the equipment, not a pass mark for one cable on its own. This does not check current-carrying capacity.