This picks a cable construction from how the run is installed, then a conductor size from the load and a resistance-only voltage drop. It does not use the current-carrying tables in BS 7671 Appendix 4. A result here is a shopping guide. Confirm the size, the protective device and the installation method in the current book before you buy or install.

The run

Socket on a ring final starts at 32 A. Use 20 A for a 20 A radial, or type the breaker rating.

Voltage drop is copper resistance at 70°C, with no reactance. Single-phase and two-phase use a go-and-return path. Three-phase uses √3. A ring final is treated as a load at the mid-point, shared both ways, so that drop is lower than the same length run as a radial. Lighting is compared with 3%. Other uses are compared with 5%, from the origin of the installation to the equipment, not for this cable on its own. Current-carrying capacity is not taken from Appendix 4.